Power Factor Correction Calculator
Enter the load, voltage and existing and target power factor to size the capacitor bank.
Step-by-step
- Enter valid values to begin.
Delta-connected capacitors assumed for the microfarad value; a wye bank needs three times the capacitance per phase for the same kVAR at the same line voltage. Resonance order is an estimate for the transformer only (utility source neglected). Verify with a harmonic study if drives or rectifiers make up more than about 20% of the load.
Power Factor Correction: Sizing Capacitors Without Creating a Resonance Problem
Core Engineering Principles
Induction motors and transformers draw two kinds of current. One does work. The other builds the magnetic field and goes back to the source every half cycle. That second one is reactive current, and it makes your meter read lower power factor than you want. A capacitor does the opposite of an inductor: it supplies reactive current locally, so the motor swaps it with the capacitor and the cable and transformer never see it. The real kW is unchanged. What drops is the kVA, and with it the current in everything upstream.
To size the capacitor, work with the power triangle. At the existing power factor the angle θ1 gives a reactive power of P × tan(θ1). At the target it’s P × tan(θ2). The difference is the kVAR you have to add. To get microfarads per phase you divide by 3 × 2πf × V² for a delta-connected bank. People forget one thing, though: a capacitor and the transformer inductance form a resonant circuit. If that resonance lands near a harmonic your drives produce, say the 5th or 7th, the bank amplifies it, and the capacitor fuses start blowing.
Resonance order h = √(kVAsc / kVARcap)
NEC & Standard References
NEC Article 460 covers capacitors: 460.8 sets conductor ampacity at 135% of the rated capacitor current, 460.8(B) covers overcurrent protection, and 460.6 requires the stored charge to drop to 50 V or less within one minute of disconnecting. IEEE 519 limits harmonic distortion at the point of common coupling and is the standard you cite when sizing detuned reactors. IEC 60831 covers low-voltage power capacitors. When harmonic loads are more than about 20% of the bus, specify a detuned bank, usually 5.67% or 7% reactor in series, so the resonance sits below the 5th harmonic.1. tan(cos−1 0.78) = 0.802; tan(cos−1 0.95) = 0.329.
2. Qc = 200 × (0.802 − 0.329) = 94.7 kVAR. Next standard bank: 100 kVAR.
3. C = 94,700 / (3 × 377 × 480²) = 363 µF per phase (delta).
4. Fault level = 500 / 0.0575 = 8,696 kVA, so h = √(8,696 / 94.7) = 9.6, comfortably away from the 5th and 7th.
- Never overcorrect. Leading PF can raise bus voltage and cause generator instability. Stay at 0.95 to 0.98.
- Switch banks in steps. A fixed bank on a lightly loaded plant overcorrects at night.
- Wait for discharge. A capacitor holds charge after you open the disconnect. Verify zero volts before touching.
- Check resonance if you have drives. Capacitor failures and nuisance trips on a plant with VFDs are almost always harmonic resonance, not bad capacitors.
- Don’t put a bank on the load side of a VFD. Correct on the line side only.
Capacitor Size in µF per Phase
| Bank | 480 V, 60 Hz | 400 V, 50 Hz |
|---|---|---|
| 25 kVAR | 96 µF | 166 µF |
| 50 kVAR | 192 µF | 332 µF |
| 100 kVAR | 384 µF | 663 µF |
| 200 kVAR | 768 µF | 1326 µF |
| 300 kVAR | 1151 µF | 1989 µF |
How Much Current Does Correction Save?
| Power factor | Current |
|---|---|
| 0.70 | 206.2 A |
| 0.80 | 180.4 A |
| 0.90 | 160.4 A |
| 0.95 | 151.9 A |
| 1.00 | 144.3 A |
Check for Harmonic Resonance
The bank and the transformer form a resonance. If it lands near the 5th or 7th harmonic, drives can overheat or blow capacitor fuses.
| Transformer | 50 kVAR | 100 kVAR | 200 kVAR | 300 kVAR |
|---|---|---|---|---|
| 500 kVA | 13.2 | 9.3 | 6.6 | 5.4 |
| 1000 kVA | 18.7 | 13.2 | 9.3 | 7.6 |
| 1500 kVA | 22.8 | 16.2 | 11.4 | 9.3 |
Worked Example: 150 kW at 0.80 to 0.95
Q = 150 × (tan(cos−1 0.80) − tan(cos−1 0.95)) = 63.2 kVAR, so a 65 kVAR step is the nearest standard size. At 400 V and 50 Hz the delta capacitance is 419 µF per phase. On a 630 kVA, 4% transformer the resonance order is 15.8, which is safely clear of the 5th and 7th harmonics.
Power Factor Correction Questions
How do I size a power factor correction bank?
Qc = P × (tan φ1 − tan φ2), using the existing and target power factors.
What target power factor should I choose?
0.95 to 0.98. Going past unity causes a leading power factor, which can raise voltage.
Why switch capacitors in steps?
A fixed bank over-corrects at light load. Automatic stepped banks follow demand.
When do I need detuned reactors?
When drives or other harmonic sources share the bus. Reactors move resonance below the 5th harmonic.
Is the bank discharged when I switch it off?
Not immediately. Wait for the discharge resistors, then measure before touching.
What savings should I expect?
Lower kVA demand, lower current, lower losses and no power factor penalty. See the power factor penalty calculator for money.