Solar Wire Voltage Drop Calculator
Enter string voltage, current, run length and conductor to get voltage drop, loss and the smallest wire for your drop limit.
Step-by-step
- Enter valid values to begin.
Resistance comes from NEC Chapter 9 Table 8 (uncoated stranded conductors at 75 °C) for AWG sizes, and from IEC 60228 class 2 maximum DC resistance at 20 °C for mm² sizes, then corrected to the entered temperature with α = 0.00323 (Cu) or 0.00330 (Al) per °C for AWG and 0.00393 / 0.00403 for mm². Aluminium mm² values are estimated as 1.64 × copper. Round-trip length is 2 × the one-way run. DC resistance only; ampacity, conduit fill, ambient derating and PV wire listings are separate checks (verify the NEC edition, Article 690 and 310).
Solar Wire Voltage Drop: What the Long Run Costs You
Core Engineering Principles
A PV string is a low-current, high-voltage circuit, but the wire still has resistance, and every ohm costs us twice because the current travels out on the positive conductor and back on the negative. That is why the formula uses the round-trip length of 2 × L. A 300 ft one-way run is 600 ft of copper. The drop is simply I × R, and it is deducted straight from the string voltage the inverter or MPPT sees. The power lost is I² × R, wasted as heat.
We usually aim for 2% or less on the DC side. Resistance climbs with temperature, about 0.4% per °C for copper, so a conductor at 75 °C carries roughly 20% more resistance than the same wire at 20 °C. Aluminium has about 1.64 times the resistance of copper at the same size. A higher string voltage cuts current and percentage drop for the same power, which is why long ground-mount runs favour longer strings. We size for ampacity first, then check drop, and take the larger conductor.
Ploss = I² × Rloop • R(T) = R75 × [1 + α (T − 75)], αCu = 0.00323
NEC & Standard References
NEC Article 690 covers photovoltaic systems. Section 690.8 sets the maximum circuit current at 125% of Isc and requires conductor ampacity of at least 125% of that value, which is about 156% of Isc. NEC Chapter 9, Table 8 lists DC resistance of stranded conductors at 75 °C, and Chapter 9 Note 2 gives the temperature coefficients. NEC Table 310.16 gives ampacity; voltage drop is a performance target, not a safety limit. IEC 60228 gives DC resistance for mm² sizes. Check the adopted edition.1. Table 8 resistance for 6 AWG: 0.491 Ω per 1000 ft.
2. Round trip = 2 × 300 = 600 ft, so R = 0.491 × 0.6 = 0.2946 Ω.
3. VD = 9.6 × 0.2946 = 2.83 V, which is 0.94% of 300 V.
4. Power loss = 9.6² × 0.2946 = 27.2 W; voltage at the load = 297.2 V.
5. Largest allowed loop resistance = 0.02 × 300 / 9.6 = 0.625 Ω, so the smallest conductor is 8 AWG (10 mm²).
6. Ampacity check: 1.25 × 1.25 × 10.2 = 15.9 A minimum after derating.
- Count both conductors. Forgetting the return leg understates the drop by half and the loss by half.
- Don’t size by drop alone. A wire that meets 2% can still fail the 690.8 ampacity check after derating.
- Hot roofs matter. Sun-heated conduit can reach 70–90 °C, adding real resistance.
- Loose terminations add drop. A hot MC4 connector is resistance you did not budget and a fire starter.
- Voltage drop lowers MPPT headroom. On cold mornings Voc is highest, so stay inside the inverter’s maximum input voltage.
Voltage Drop for a 300 ft Run
The numbers below use the page’s Table 8 copper resistance and the round-trip length. Moving up a few wire sizes cuts loss sharply.
| Wire | Loop R | Voltage drop | % of 300 V | Power loss |
|---|---|---|---|---|
| 12 AWG | 1.1580 Ω | 11.12 V | 3.71% | 106.7 W |
| 10 AWG | 0.7260 Ω | 6.97 V | 2.32% | 66.9 W |
| 8 AWG | 0.4584 Ω | 4.40 V | 1.47% | 42.2 W |
| 6 AWG | 0.2946 Ω | 2.83 V | 0.94% | 27.2 W |
| 4 AWG | 0.1848 Ω | 1.77 V | 0.59% | 17.0 W |
| 2 AWG | 0.1164 Ω | 1.12 V | 0.37% | 10.7 W |
| 1/0 AWG | 0.0732 Ω | 0.70 V | 0.23% | 6.7 W |
Maximum Run Length for 2% Drop
Read across by current and down by wire size. For the PV source circuit, the current used is the string Imp, or 125% of Isc if you want a conservative design.
| Wire | 5 A | 8 A | 10 A | 12 A | 15 A |
|---|---|---|---|---|---|
| 14 AWG | 195 | 122 | 98 | 81 | 65 |
| 12 AWG | 311 | 194 | 155 | 130 | 104 |
| 10 AWG | 496 | 310 | 248 | 207 | 165 |
| 8 AWG | 785 | 491 | 393 | 327 | 262 |
| 6 AWG | 1,222 | 764 | 611 | 509 | 407 |
| 4 AWG | 1,948 | 1,218 | 974 | 812 | 649 |
| 2 AWG | 3,093 | 1,933 | 1,546 | 1,289 | 1,031 |
| 1/0 AWG | 4,918 | 3,074 | 2,459 | 2,049 | 1,639 |
Why Higher Voltage Helps
Doubling the string voltage lets you double the run length for the same wire and current. This is why long ground-mount rows use longer strings.
| System voltage | 10 AWG | 6 AWG |
|---|---|---|
| 48 V | 40 ft | 98 ft |
| 150 V | 124 ft | 305 ft |
| 300 V | 248 ft | 611 ft |
| 600 V | 496 ft | 1,222 ft |
| 1000 V | 826 ft | 2,037 ft |
Worked Example: Upsizing to 4 AWG
Take the 300 ft run with 9.6 A at 300 V. On 6 AWG the drop is 2.83 V (0.94%) and the loss is 27.2 W. On 4 AWG the loop resistance falls to 0.1848 Ω, the drop to 1.77 V (0.59%) and the loss to 17.0 W. At 6 hours of full output a day that saves about 22 kWh a year, which you compare with the extra copper cost.
Solar Wire Questions
Why is the length doubled in the formula?
Current flows out on the positive conductor and returns on the negative, so the resistance counts both conductors: R = resistance per length × 2L.
What voltage drop is acceptable for solar DC wiring?
Designers usually aim for 2% or less on the DC side. It is a performance target, not a safety limit.
Do I size for voltage drop or ampacity first?
Ampacity first, then check the drop, and take the larger conductor. NEC 690.8 requires 125% × 125% of Isc.
Does temperature matter?
Yes. Copper resistance rises about 0.4% per °C, so a hot conductor loses more voltage than the cold table value.
Is aluminium acceptable?
It is used on large arrays. It has about 1.64 times the resistance of copper at the same size, so choose a larger gauge.
How does a higher string voltage help?
The same power flows at lower current, so the percentage drop falls and longer runs are possible.