Solar & EVNEC 690 • NEC Ch.9 Table 8

Solar Wire Voltage Drop Calculator

Enter string voltage, current, run length and conductor to get voltage drop, loss and the smallest wire for your drop limit.

VD = 2 × I × R × L  •  % = VD / Vmp × 100  •  Ploss = I² × R
Calculated Result
—

Step-by-step

  1. Enter valid values to begin.

Resistance comes from NEC Chapter 9 Table 8 (uncoated stranded conductors at 75 °C) for AWG sizes, and from IEC 60228 class 2 maximum DC resistance at 20 °C for mm² sizes, then corrected to the entered temperature with α = 0.00323 (Cu) or 0.00330 (Al) per °C for AWG and 0.00393 / 0.00403 for mm². Aluminium mm² values are estimated as 1.64 × copper. Round-trip length is 2 × the one-way run. DC resistance only; ampacity, conduit fill, ambient derating and PV wire listings are separate checks (verify the NEC edition, Article 690 and 310).

NEC 690 • NEC Ch.9 Table 8 • DC Voltage Drop

Solar Wire Voltage Drop: What the Long Run Costs You

Core Engineering Principles

A PV string is a low-current, high-voltage circuit, but the wire still has resistance, and every ohm costs us twice because the current travels out on the positive conductor and back on the negative. That is why the formula uses the round-trip length of 2 × L. A 300 ft one-way run is 600 ft of copper. The drop is simply I × R, and it is deducted straight from the string voltage the inverter or MPPT sees. The power lost is I² × R, wasted as heat.

We usually aim for 2% or less on the DC side. Resistance climbs with temperature, about 0.4% per °C for copper, so a conductor at 75 °C carries roughly 20% more resistance than the same wire at 20 °C. Aluminium has about 1.64 times the resistance of copper at the same size. A higher string voltage cuts current and percentage drop for the same power, which is why long ground-mount runs favour longer strings. We size for ampacity first, then check drop, and take the larger conductor.

VD = I × Rloop = I × Rper length × 2L  •  %VD = VD / Vmp × 100
Ploss = I² × Rloop  •  R(T) = R75 × [1 + α (T − 75)], αCu = 0.00323

NEC & Standard References

NEC Article 690 covers photovoltaic systems. Section 690.8 sets the maximum circuit current at 125% of Isc and requires conductor ampacity of at least 125% of that value, which is about 156% of Isc. NEC Chapter 9, Table 8 lists DC resistance of stranded conductors at 75 °C, and Chapter 9 Note 2 gives the temperature coefficients. NEC Table 310.16 gives ampacity; voltage drop is a performance target, not a safety limit. IEC 60228 gives DC resistance for mm² sizes. Check the adopted edition.
Worked Example: 300 ft String Run in 6 AWG Copper
Given: Vmp 300 V, Imp 9.6 A, Isc 10.2 A, 300 ft one way, 6 AWG copper at 75 °C, 2% limit.
1. Table 8 resistance for 6 AWG: 0.491 Ω per 1000 ft.
2. Round trip = 2 × 300 = 600 ft, so R = 0.491 × 0.6 = 0.2946 Ω.
3. VD = 9.6 × 0.2946 = 2.83 V, which is 0.94% of 300 V.
4. Power loss = 9.6² × 0.2946 = 27.2 W; voltage at the load = 297.2 V.
5. Largest allowed loop resistance = 0.02 × 300 / 9.6 = 0.625 Ω, so the smallest conductor is 8 AWG (10 mm²).
6. Ampacity check: 1.25 × 1.25 × 10.2 = 15.9 A minimum after derating.
Safety & Installation Rules
  • Count both conductors. Forgetting the return leg understates the drop by half and the loss by half.
  • Don’t size by drop alone. A wire that meets 2% can still fail the 690.8 ampacity check after derating.
  • Hot roofs matter. Sun-heated conduit can reach 70–90 °C, adding real resistance.
  • Loose terminations add drop. A hot MC4 connector is resistance you did not budget and a fire starter.
  • Voltage drop lowers MPPT headroom. On cold mornings Voc is highest, so stay inside the inverter’s maximum input voltage.

Voltage Drop for a 300 ft Run

The numbers below use the page’s Table 8 copper resistance and the round-trip length. Moving up a few wire sizes cuts loss sharply.

300 ft one-way (600 ft round trip), 9.6 A, 300 V string, copper at 75 °C resistance (NEC Chapter 9 Table 8).
WireLoop RVoltage drop% of 300 VPower loss
12 AWG1.1580 Ω11.12 V3.71%106.7 W
10 AWG0.7260 Ω6.97 V2.32%66.9 W
8 AWG0.4584 Ω4.40 V1.47%42.2 W
6 AWG0.2946 Ω2.83 V0.94%27.2 W
4 AWG0.1848 Ω1.77 V0.59%17.0 W
2 AWG0.1164 Ω1.12 V0.37%10.7 W
1/0 AWG0.0732 Ω0.70 V0.23%6.7 W

Maximum Run Length for 2% Drop

Read across by current and down by wire size. For the PV source circuit, the current used is the string Imp, or 125% of Isc if you want a conservative design.

Maximum one-way run in feet for a 2% drop on a 300 V string.
Wire5 A8 A10 A12 A15 A
14 AWG195122988165
12 AWG311194155130104
10 AWG496310248207165
8 AWG785491393327262
6 AWG1,222764611509407
4 AWG1,9481,218974812649
2 AWG3,0931,9331,5461,2891,031
1/0 AWG4,9183,0742,4592,0491,639

Why Higher Voltage Helps

Doubling the string voltage lets you double the run length for the same wire and current. This is why long ground-mount rows use longer strings.

Maximum one-way run for a 2% drop at 10 A. The longer the string, the longer the run.
System voltage10 AWG6 AWG
48 V40 ft98 ft
150 V124 ft305 ft
300 V248 ft611 ft
600 V496 ft1,222 ft
1000 V826 ft2,037 ft

Worked Example: Upsizing to 4 AWG

Take the 300 ft run with 9.6 A at 300 V. On 6 AWG the drop is 2.83 V (0.94%) and the loss is 27.2 W. On 4 AWG the loop resistance falls to 0.1848 Ω, the drop to 1.77 V (0.59%) and the loss to 17.0 W. At 6 hours of full output a day that saves about 22 kWh a year, which you compare with the extra copper cost.

Solar Wire Questions

Why is the length doubled in the formula?

Current flows out on the positive conductor and returns on the negative, so the resistance counts both conductors: R = resistance per length × 2L.

What voltage drop is acceptable for solar DC wiring?

Designers usually aim for 2% or less on the DC side. It is a performance target, not a safety limit.

Do I size for voltage drop or ampacity first?

Ampacity first, then check the drop, and take the larger conductor. NEC 690.8 requires 125% × 125% of Isc.

Does temperature matter?

Yes. Copper resistance rises about 0.4% per °C, so a hot conductor loses more voltage than the cold table value.

Is aluminium acceptable?

It is used on large arrays. It has about 1.64 times the resistance of copper at the same size, so choose a larger gauge.

How does a higher string voltage help?

The same power flows at lower current, so the percentage drop falls and longer runs are possible.