DC Solar Cable Calculator
Enter system voltage, current and run length to get the smallest cable that passes both ampacity and voltage drop.
Step-by-step
- Enter valid values to begin.
Voltage drop uses VD = 2 × K × I × L / CM, the same formula used for DC and single-phase AC. Ampacity uses NEC Table 310.16 with the ambient correction from 310.15(B). PV wire and exposed rooftop conditions (up to 70°C+) need the 690.31 adjustments — use the Cable Size calculator for those.
DC Solar Cable Sizing: Why 12 Volts Is Brutal on Wire
Core Engineering Principles
This is where voltage drop bites hardest. On a 12 V system, a 3% drop is only 0.36 V, and a battery cable that loses half a volt is running at 4% loss while the inverter sees 11.5 V and starts alarming. Because the current at 12 V is four times what it would be at 48 V for the same watts, the same wire loses sixteen times the power. That’s why every serious off-grid install is 24 V or 48 V and why the charge controller run to the battery bank is always the shortest cable you can manage.
The formula is the same one used for AC single-phase: VD = 2 × K × I × L / CM, with L as the one-way distance. For solar there are two checks. Voltage drop usually controls on short, high-current runs like the battery cable, and ampacity usually controls on long, higher-voltage PV strings. The page runs both and tells you which one sets the size. For PV source circuits the NEC multiplies the short-circuit current by 125% twice, 1.25 × 1.25 = 1.56, because the irradiance can exceed the rating and the circuit is continuous.
PV source circuit: Idesign = Isc × 1.25 × 1.25 • Battery / controller: I × 1.25 (continuous)
NEC & Standard References
NEC 690.8(A) sets the maximum PV circuit current as 125% of Isc, and 690.8(B) applies another 125% for conductor and overcurrent sizing, so the conductors must carry 156% of Isc. 690.31 covers PV wiring methods; exposed single-conductor PV wire and USE-2 are rated 90°C wet. 310.16 gives ampacities and 310.15(B) gives the ambient correction. Sunlit rooftop raceways run much hotter than the air, so use a higher ambient. Article 706 covers energy storage and battery cable sizing, and the manufacturer’s installation manual often specifies the cable length and size for the inverter. The 3% voltage drop value is only a recommendation in 210.19(A) IN 4, but many inverter and controller manuals require 1–2%.1. Design current: 50 × 1.25 = 62.5 A. Ampacity: 6 AWG at 75°C = 65 A, so 6 AWG passes.
2. Allowed drop: 24 × 3% = 0.72 V.
3. Required area: 2 × 12.9 × 50 × 15 / 0.72 = 26,875 CM. 6 AWG is 26,240, just short, so voltage drop needs 4 AWG (41,740 CM).
4. Actual drop on 4 AWG = 19,350 / 41,740 = 0.46 V (1.93%).
Ampacity said 6 AWG, voltage drop said 4 AWG. Drop controls.
- Get the length right. It’s the one-way distance from the controller to the battery.
- Use a fuse or breaker rated for DC. AC breakers can’t break DC arcs reliably. Look for a DC rating of at least the system voltage.
- Crimps matter. Heavy battery cables need hydraulic or properly rated lugs and heat-shrink; a poor crimp is the usual cause of melted battery terminals.
- Don’t use cheap copper-clad wire. It carries less than the table assumes. Use real copper, preferably fine-stranded.
- Hot roof, hot wire. Rooftop PV wire runs at 60–70°C. Use the ambient field and check the 90°C column.
Maximum Cable Length for 2% Drop at 12 V
At 12 V a 2% drop is only 0.24 V, so the runs are short. The table gives the longest one-way run in feet for common wire sizes and currents. It uses the same VD = 2 × K × I × L / CM formula as the calculator.
| Wire | 10 A | 20 A | 30 A | 40 A | 60 A |
|---|---|---|---|---|---|
| 14 AWG | 4 | 2 | 1 | 1 | 1 |
| 12 AWG | 6 | 3 | 2 | 2 | 1 |
| 10 AWG | 10 | 5 | 3 | 2 | 2 |
| 8 AWG | 15 | 8 | 5 | 4 | 3 |
| 6 AWG | 24 | 12 | 8 | 6 | 4 |
| 4 AWG | 39 | 19 | 13 | 10 | 6 |
| 2 AWG | 62 | 31 | 21 | 15 | 10 |
| 1/0 AWG | 98 | 49 | 33 | 25 | 16 |
| 2/0 AWG | 124 | 62 | 41 | 31 | 21 |
| 4/0 AWG | 197 | 98 | 66 | 49 | 33 |
The Same Check at 24 V and 48 V
Doubling the voltage doubles the allowed volts and halves the current for the same watts, so the permitted length grows four times. Here are the distances at 2% for 24 V and 48 V.
| Wire | 10 A | 20 A | 30 A | 40 A | 60 A |
|---|---|---|---|---|---|
| 14 AWG | 8 | 4 | 3 | 2 | 1 |
| 12 AWG | 12 | 6 | 4 | 3 | 2 |
| 10 AWG | 19 | 10 | 6 | 5 | 3 |
| 8 AWG | 31 | 15 | 10 | 8 | 5 |
| 6 AWG | 49 | 24 | 16 | 12 | 8 |
| 4 AWG | 78 | 39 | 26 | 19 | 13 |
| 2 AWG | 123 | 62 | 41 | 31 | 21 |
| 1/0 AWG | 196 | 98 | 65 | 49 | 33 |
| 2/0 AWG | 248 | 124 | 83 | 62 | 41 |
| 4/0 AWG | 394 | 197 | 131 | 98 | 66 |
| Wire | 10 A | 20 A | 30 A | 40 A | 60 A |
|---|---|---|---|---|---|
| 14 AWG | 15 | 8 | 5 | 4 | 3 |
| 12 AWG | 24 | 12 | 8 | 6 | 4 |
| 10 AWG | 39 | 19 | 13 | 10 | 6 |
| 8 AWG | 61 | 31 | 20 | 15 | 10 |
| 6 AWG | 98 | 49 | 33 | 24 | 16 |
| 4 AWG | 155 | 78 | 52 | 39 | 26 |
| 2 AWG | 247 | 123 | 82 | 62 | 41 |
| 1/0 AWG | 393 | 196 | 131 | 98 | 65 |
| 2/0 AWG | 495 | 248 | 165 | 124 | 83 |
| 4/0 AWG | 787 | 394 | 262 | 197 | 131 |
Quick Examples
100 W panel to a 12 V controller, 8 ft: about 6 A, so 12 AWG gives roughly 10 ft at 2%, well inside the run. 400 W array on a 24 V battery, 15 ft run: about 17 A, and 8 AWG allows 18 ft at 2%. PV string with Isc = 10 A: the NEC design current is 10 × 1.25 × 1.25 = 15.6 A, so the wire must be sized for at least that, then checked for drop.
Why Higher Voltage Saves Copper
Power lost in the wire is I²R. For a 1,200 W load the current is 100 A at 12 V but only 25 A at 48 V, so the same wire wastes 16 times less power at 48 V. This is why larger solar systems moved to 24 V and 48 V batteries.
Rule values are examples from standard circular mil areas. Always confirm with the cable maker’s data and the NEC edition your inspector uses.
Solar Cable Questions
What size wire do I need for a 12 V solar system?
It depends on the current and the run length. For a 20 A circuit with a 10 ft one-way run, 8 AWG copper keeps the drop under 2% (8 ft max). Use the calculator above to check your own numbers, and size for the larger of the voltage drop and ampacity results.
How much voltage drop is acceptable in a solar system?
Many designers use 2% for the battery and charge controller wiring, and up to 3% for other circuits, with 5% as an upper limit on PV source circuits. Inverter and charge controller manuals often require 1–2%, so check the manual first.
Why does the NEC multiply the PV short-circuit current by 1.25 twice?
One 125% factor allows for irradiance above the rated 1,000 W/m², and the other treats the circuit as continuous. The result is 1.56 times Isc, which is the minimum current the conductors and overcurrent device must handle.
Should I use copper or aluminum cable for solar?
Copper is the usual choice for short battery and controller runs because it has lower resistance (K = 12.9 against 21.2) and terminates more reliably. Aluminum can make sense for long, large-size runs if the terminals are rated for it.
Is voltage drop worse at 12 V than at 48 V?
Yes. The same power needs four times the current at 12 V, and the allowed drop in volts is four times smaller, so for a given wire the permitted length is 16 times shorter at 12 V than at 48 V.
Does temperature change the cable size?
It changes the ampacity, not the voltage drop formula. Hot roofs and conduit in sunlight need a temperature correction under NEC 310.15(B), so a larger conductor may be needed than the drop calculation alone suggests.