Industrial & 3-PhaseIEC 61439-1 / ANSI C37.20 / UL 891

Switchgear Busbar Capacity Calculator

Enter bar size, material, number of bars and temperature limits to get continuous ampacity and short-circuit withstand.

I ≈ 20.4 × θ0.61 × p0.39 × A0.5  •  Ith = k × A / √t
Calculated Result
—

Step-by-step

  1. Enter valid values to begin.

Continuous rating is an empirical fit to DIN 43671 free-air copper bar data (about ±10%). Multi-bar factors (1, 1.8, 2.4, 2.9) assume bar spacing equal to bar thickness. Manufacturer tested ratings and the assembly standard (IEC 61439-1, UL 891) override this estimate.

IEC 61439-1 • IEC 60865 • ANSI C37.20 • Switchgear Busbars

Switchgear Busbar Capacity: Ampacity Is a Heat Problem, Not a Cross-Section Problem

Core Engineering Principles

Rectangular copper bar looks simple, but its current rating depends on how well it sheds heat. A bar produces I²R heat through its whole volume and loses it through its surface by convection and radiation. A flat, wide bar has more surface per unit of area than a square one, so it carries more current for the same copper. That’s why the bar is wide and thin, why two thin bars with a gap carry more than one thick one, and why a painted bar runs cooler than a bright one, since a dull surface radiates better.

The standard tables come from tests: a certain temperature rise over ambient, vertical orientation, in free air. This page uses a curve fitted to the DIN 43671 copper bar data. Current scales with the square root of cross-section, the 0.39 power of perimeter and the 0.61 power of temperature rise. Aluminum is about 78% of copper for the same size. Real switchgear in an enclosure runs less than the free-air rating, so a derating factor is applied. The bar must also carry the fault. The short-time current rating, usually one second, is set by how much heat the bar can absorb without softening: I = k × A / √t.

Icont ≈ 20.4 × θ0.61 × p0.39 × A0.5 (Cu, A in cm², p in cm)  •  Al = 0.78 × Cu
Short-time Ith = k × A / √t, k ≈ 143 (Cu) or 94 (Al) A·√s/mm²

NEC & Standard References

IEC 61439-1 sets temperature-rise limits for assemblies: 70 K at terminals for external conductors, and the busbars may run hotter if adjacent insulation permits. ANSI C37.20.1 covers metal-enclosed low-voltage switchgear with a 65 °C rise at 40 °C ambient on bus bars, and silver or tin plating at joints. IEC 60865-1 gives the thermal and mechanical short-circuit calculation, and UL 891 covers switchboards. NEC 408.30 through 408.56 cover switchboard construction, and 408.36 requires the panel’s overcurrent protection. A manufacturer’s tested rating always overrides a calculated number like the one on this page.
Worked Example: 100 × 10 mm Copper Bar, 30 K Rise
Given: one 100 mm × 10 mm copper bar per phase, 35 °C ambient, 65 °C maximum, vertical, free air.
1. Area = 10 cm²; perimeter = 22 cm; rise θ = 30 K.
2. I = 20.4 × 300.61 × 220.39 × 100.5 = 20.4 × 7.96 × 3.34 × 3.16 = 1,715 A.
3. In an enclosure derated to 0.80: 1,372 A.
4. Short-time (1 s): 143 × 1,000 mm² / 1 = 143 kA thermal withstand.
Rated for a 1,200 A main with margin; for 1,600 A you’d go to two bars per phase.
Safety & Installation Rules
  • Joints are the weak point. Plate, torque and re-torque bolted joints; a poor joint can run 30 K hotter than the bar.
  • Vertical vs flat. A horizontal bar flat on its side loses 10 to 15% of its rating.
  • Skin and proximity effect matter above about 10 mm thickness at 60 Hz; multiple bars are often more effective than one thick bar.
  • Bracing. Short-circuit forces try to bend the bar. Spacing of the supports determines the peak current rating, not just the thermal rating.
  • Infrared scan every year. Hot joints are the leading cause of switchgear fires.

Continuous Current

One bar per phase, vertical, free air, 30 K rise. Aluminium is 78% of copper. The last column is copper derated to 0.80 in an enclosure.
BarAreaCopperAluminiumCu in enclosure
40 × 5 mm2.0 cm²541 A422 A433 A
50 × 5 mm2.5 cm²654 A510 A523 A
60 × 10 mm6.0 cm²1114 A869 A891 A
80 × 10 mm8.0 cm²1418 A1106 A1135 A
100 × 10 mm10.0 cm²1715 A1338 A1372 A
120 × 10 mm12.0 cm²2005 A1564 A1604 A

Temperature Rise

100 × 10 mm copper bar for different temperature rises.
RiseFree airEnclosure (0.80)
20 K1339 A1071 A
30 K1715 A1372 A
40 K2044 A1635 A
50 K2342 A1873 A

Fault Withstand

The bar must carry the fault as well as the load.

Short-time current I = k A / √t for copper (k = 143) and 1 s aluminium (k = 94).
BarCu 1 sCu 3 sAl 1 s
40 × 5 mm28.6 kA16.5 kA18.8 kA
50 × 5 mm35.8 kA20.6 kA23.5 kA
60 × 10 mm85.8 kA49.5 kA56.4 kA
80 × 10 mm114.4 kA66.0 kA75.2 kA
100 × 10 mm143.0 kA82.6 kA94.0 kA
120 × 10 mm171.6 kA99.1 kA112.8 kA

Worked Example: 60 × 10 mm Copper at 40 K

Area = 6 cm² and perimeter = 14 cm. I = 20.4 × 400.61 × 140.39 × 60.5 = 1327 A in free air, or 1062 A at 0.80 in an enclosure. One-second withstand is 143 × 600 / 1000 = 85.8 kA for copper. For a 1,000 A main this size works with margin on current; check the fault level against the rating.

Busbar Questions

How is bus bar current estimated?

I = 20.4 × θ0.61 × p0.39 × A0.5 for copper, with A in cm² and p in cm.

Why derate in an enclosure?

Less airflow means higher temperature, so the free-air rating is multiplied by about 0.8.

Copper or aluminium?

Aluminium carries about 78% of the current of copper for the same size.

What is the short-time rating?

Typically the one-second current the bar can carry without softening, I = k A / √t.

Do more bars per phase help?

Yes, but not linearly, because of proximity effect.

Is this a manufacturer rating?

No. It is an estimate. Use the switchgear manufacturer’s tested rating for design.