Three-Phase Motor Current Calculator

Enter the motor rating, voltage, power factor and efficiency to get formula amps beside the NEC table value.

IFLA = (HP × 746) / (√3 × V × PF × η)
Calculated Result
—

Step-by-step

  1. Enter valid values to begin.

NEC Table 430.250 is shown for comparison where the voltage is a standard NEC column (200, 208, 230, 460, 575 V) and the horsepower is a table value. Use the table value for conductors, disconnect and short-circuit protection; use the nameplate for the overload relay.

NEC 430.250 • NEMA MG-1 • Motor Full-Load Current

Three-Phase Motor Current: Formula Amps vs. Table Amps

Core Engineering Principles

A motor’s shaft takes mechanical horsepower and the supply has to deliver more than that, because the motor isn’t 100% efficient and it needs magnetizing current. One horsepower is 746 W of output. Divide by efficiency and you have the real input watts. Divide again by the power factor and the √3 × V and you have the line current. That’s the formula on this page, and it’s what you would measure with a clamp meter on a motor running at full load.

Here is the part that surprises new engineers: the formula amps and the table amps are often different, and the code wants the table. A modern premium-efficiency motor may draw 57 A where the NEC table says 65 A for the same 50 HP at 460 V. Both are right. The nameplate and the formula describe the motor you bought; Table 430.250 is a conservative standard that makes sure conductors and breakers don’t depend on which brand was installed.

IFLA = (HP × 746) / (√3 × V × PF × η)  •  kW input = kW out / η
Conductor = 125% × table FLC (430.22)  •  Overload = 115–125% × nameplate (430.32)

NEC & Standard References

NEC 430.6(A)(1) requires that conductor ampacity, switch ratings and branch-circuit short-circuit protection come from Table 430.250 for three-phase motors, not the nameplate. 430.6(A)(2) says the overload relay uses the nameplate full-load current. 430.22 sizes the branch conductors at 125%, and 430.110 sizes the disconnect at 115% of table FLC. NEMA MG-1 publishes the efficiency levels (NEMA Premium) and service factors, and IEEE 112 covers the efficiency test method. Typical power factor runs from 0.80 on small motors to 0.90 on large, and drops sharply when the motor is lightly loaded.
Worked Example: 50 HP, 460 V, Premium-Efficiency Motor
Given: 50 HP, 460 V, 3φ, PF 0.88, efficiency 93%.
1. Output: 50 × 746 = 37,300 W.
2. Denominator: 1.732 × 460 × 0.88 × 0.93 = 652.0.
3. IFLA = 37,300 / 652.0 = 57.2 A (formula).
4. NEC Table 430.250 for 50 HP at 460 V = 65 A. Use 65 A for the conductor (65 × 1.25 = 81.3 A) and the short-circuit device.
5. Overload relay: nameplate amps × 1.15 or 1.25, not the table.
Safety & Installation Rules
  • Don’t size the breaker from the clamp reading. A motor at 70% load might read 42 A. That’s not the number the code uses.
  • Low voltage means high current. A 460 V motor on a 430 V bus draws about 7% more current for the same shaft load and runs hotter.
  • Check the PF and efficiency on the nameplate. Old rewound motors can be 85% efficient or worse.
  • Lightly loaded motors. Power factor falls under 50% load; the current doesn’t fall as much as you expect, because magnetizing current stays.

Motor Current by Horsepower at 460 V

NEC Table 430.250 full-load current for three-phase induction motors at 460 V, the 125% conductor figure (430.22), and the formula with PF 0.88 and 93% efficiency.
MotorNEC FLCConductor 125%Formula current
10 HP14 A17.5 A11.4 A
15 HP21 A26.2 A17.2 A
20 HP27 A33.8 A22.9 A
25 HP34 A42.5 A28.6 A
30 HP40 A50.0 A34.3 A
40 HP52 A65.0 A45.8 A
50 HP65 A81.2 A57.2 A
60 HP77 A96.2 A68.6 A
75 HP96 A120.0 A85.8 A
100 HP124 A155.0 A114.4 A
125 HP156 A195.0 A143.0 A
150 HP180 A225.0 A171.6 A
200 HP240 A300.0 A228.8 A

Low Voltage Raises Current

Current increase for the same shaft load on a lower supply voltage.
SupplyCurrent vs 460 V
460 V0.0%
440 V4.5%
430 V7.0%
414 V11.1%
400 V15.0%

Table Current, Nameplate or Measured?

The code uses table values for conductors and short-circuit protection, and nameplate values for overload relays.

Which number to use.
PurposeCurrent to use
Conductor size125% of Table 430.250 FLC
Short-circuit deviceTable FLC with the multiplier in 430.52
Overload relay115–125% of nameplate amps (430.32)
Energy and costMeasured current and power

Worked Example: 25 HP Motor at 460 V

Table FLC is 34 A, so the conductor must carry 34 × 1.25 = 42.5 A. The formula with PF 0.88 and 93% efficiency gives 28.6 A, which is lower, as is typical. For the overload relay, a nameplate of 32 A at 1.15 gives 36.8 A. On a 430 V bus the same load would draw about 7% more current.

Motor Current Questions

How do I calculate motor full-load current?

I = HP × 746 / (√3 × V × PF × efficiency).

Why does the NEC table differ from the formula?

The table uses standard values so conductors and breakers do not depend on the brand. Real motors often draw less.

Which current do I use for the overload relay?

The nameplate current, times 1.15 or 1.25 depending on the motor.

What happens if the voltage is low?

The motor draws more current for the same output and runs hotter.

Does the formula work for single-phase?

No. Use 1/V × PF × efficiency without the √3.

How does starting current compare?

Locked-rotor current is typically six to eight times full load. See the motor starting current calculator.