Voltage Drop Calculator
Check conductor voltage drop against the NEC 3% branch-circuit and 5% total recommendations, and find the smallest compliant wire size.
Step-by-step
- Enter valid values to begin.
K = 12.9 (copper) and 21.2 (aluminum) Ω·cmil/ft are the approximate values at 75°C used in NEC informational notes. The AC impedance estimate uses approximate NEC Chapter 9, Table 9 resistance and reactance values (aluminum resistance scaled from copper); use the printed tables for final design.
Voltage Drop: Why the Light at the End of the Run Is Dim
Core Engineering Principles
Copper is a good conductor but it is not a perfect one. Every foot of wire has resistance, so when current flows some of the voltage is used up in the cable before it ever reaches the load. The longer the run and the heavier the current, the more you lose. At the far end a motor runs hot because it draws more current to make up for low voltage, lights look yellow, and electronics reset for no obvious reason. Equipment that seems faulty is often fine, and the real problem is a long run of undersized wire such as 150 feet of 12 AWG.
The usual formula uses circular mils: VD = 2 × K × I × L / CM. K is the resistivity of the metal in ohm-circular-mils per foot (about 12.9 for copper, 21.2 for aluminum at 75°C), L is the one-way distance, and the 2 accounts for the trip out and back. Three-phase swaps the 2 for 1.732. Single-phase and DC use the same formula, which is why the DC solar page uses it too. On AC the wire also has inductive reactance, especially in steel conduit, so the page adds an impedance estimate using your power factor and conduit type. For big conductors the reactance term matters more than resistance.
% drop = VD / Vsource × 100 • K(Cu) = 12.9, K(Al) = 21.2
NEC & Standard References
The NEC doesn’t make voltage drop mandatory for most circuits, which surprises a lot of people. 210.19(A) Informational Note 4 recommends no more than 3% on a branch circuit and 215.2(A) Informational Note 2 recommends 3% on a feeder, with 5% total from the service to the farthest outlet. Informational notes aren’t enforceable, but engineers write them into specs and some jurisdictions adopt them, so treat 3% as the number to hit. Where it is required: fire pump feeders (695.7), and sometimes the manufacturer’s installation instructions for the equipment itself. The resistance and reactance values live in Chapter 9, Table 9, and conductor areas in Table 8.
1. 12 AWG (6,530 CM): VD = 2 × 12.9 × 20 × 100 / 6,530 = 7.90 V = 6.58% — fails.
2. 10 AWG (10,380 CM): VD = 51,600 / 10,380 = 4.97 V = 4.14% — still fails.
3. 8 AWG (16,510 CM): VD = 51,600 / 16,510 = 3.13 V = 2.60% — passes.
The 12 AWG wire is legal for a 20 A breaker, and a compressor on the far end would still struggle to start on 112 V. Go to 8 AWG, and remember the equipment grounding conductor has to go up with it under 250.122(B).
- One-way length only. The formula already doubles it. A common slip is entering the round-trip distance, which makes every result look oversized.
- Motors care about starting drop. A motor draws five to seven times its running current for a second or two. Check the drop at that current if it’s a pump or compressor.
- Upsized wire still has to fit the lugs. Check the terminal range on the breaker and equipment before you order, per 110.14(C).
How Much Voltage Drop Is Allowed?
There is no single worldwide number. The NEC recommends 3% on a branch circuit and 5% from the service to the last outlet, as informational notes. In the UK, BS 7671 suggests 3% for lighting and 5% for other uses, measured from the origin of the installation. IEC 60364 offers 4% as an example, and AS/NZS 3000 allows 5% overall. Always check the equipment too: some drives, LED drivers and sensitive electronics want less than the installation rule gives you.
Voltage Drop in mm² (Metric Cable Sizes)
Outside North America cables are sold in mm², and the usual shortcut is the voltage drop per amp per metre. Multiply it by the current in amps and the one-way length in metres, then divide by 1000 to get volts. Behind the number is the same physics as the formula above: for a single-phase circuit it is 2 × ρ × 1000 / A, where ρ is about 0.022 Ω·mm²/m for copper at 70°C (aluminium is about 0.036) and A is the cross-section in mm².
| Cable size | Single-phase / DC (mV/A/m) | Three-phase (mV/A/m) |
|---|---|---|
| 1.5 mm² | 29.0 | 25.1 |
| 2.5 mm² | 17.7 | 15.4 |
| 4 mm² | 11.0 | 9.55 |
| 6 mm² | 7.37 | 6.38 |
| 10 mm² | 4.38 | 3.79 |
| 16 mm² | 2.75 | 2.38 |
| 25 mm² | 1.74 | 1.51 |
| 35 mm² | 1.25 | 1.09 |
| 50 mm² | 0.926 | 0.802 |
| 70 mm² | 0.641 | 0.555 |
| 95 mm² | 0.462 | 0.400 |
| 120 mm² | 0.366 | 0.317 |
1. 2.5 mm²: VD = 17.7 × 20 × 25 / 1000 = 8.9 V = 3.9% — over a 3% limit, though still under 5%.
2. 4 mm²: VD = 11.0 × 20 × 25 / 1000 = 5.5 V = 2.4% — passes a 3% limit.
Going up one size fixes it, and the bigger cable also runs cooler.
Maximum Cable Length for 3% Drop
The longest one-way run that keeps the drop within 3% for copper cable on a single-phase 230 V supply. Lengths are in metres, rounded.
| Cable size | 10 A | 16 A | 20 A | 25 A | 32 A |
|---|---|---|---|---|---|
| 1.5 mm² | 24 | 15 | 12 | 10 | 7 |
| 2.5 mm² | 39 | 24 | 19 | 16 | 12 |
| 4 mm² | 63 | 39 | 31 | 25 | 20 |
| 6 mm² | 94 | 59 | 47 | 37 | 29 |
| 10 mm² | 158 | 98 | 79 | 63 | 49 |
| 16 mm² | 251 | 157 | 125 | 100 | 78 |
| 25 mm² | 397 | 248 | 198 | 159 | 124 |
The same idea for a three-phase 400 V supply (3% is 12 V line to line). Lengths in metres, rounded.
| Cable size | 10 A | 16 A | 20 A | 25 A | 32 A |
|---|---|---|---|---|---|
| 1.5 mm² | 48 | 30 | 24 | 19 | 15 |
| 2.5 mm² | 78 | 49 | 39 | 31 | 24 |
| 4 mm² | 126 | 79 | 63 | 50 | 39 |
| 6 mm² | 188 | 117 | 94 | 75 | 59 |
| 10 mm² | 316 | 198 | 158 | 127 | 99 |
| 16 mm² | 504 | 315 | 252 | 201 | 157 |
| 25 mm² | 796 | 498 | 398 | 319 | 249 |
If you work in AWG: 14 AWG ≈ 2.1 mm², 12 AWG ≈ 3.3 mm², 10 AWG ≈ 5.3 mm², 8 AWG ≈ 8.4 mm², 6 AWG ≈ 13.3 mm², 4 AWG ≈ 21.2 mm², 2 AWG ≈ 33.6 mm², 1/0 AWG ≈ 53.5 mm². Use the nearest standard metric size up when converting.
Three-Phase Voltage Drop
A balanced three-phase circuit carries the current in three conductors that partly cancel, so the loss per amp is lower: the factor is 1.732 (√3) instead of 2. Take the percentage against the line-to-line voltage. For 400 V that means a 3% limit of 12 V, and for 208 V it is 6.2 V. Choose Three-phase in the calculator above and enter the line current and the one-way length.
12 V and Other DC Circuits
Low-voltage DC is where voltage drop hurts most, because the allowed loss is tiny: 3% of 12 V is only 0.36 V. Take a 12 V pump drawing 10 A on a 5 m run (one way): 4 mm² copper drops about 0.55 V (4.6%), 6 mm² about 0.37 V (3.1%), and 10 mm² about 0.22 V (1.8%). Pick DC in the calculator for the same check in AWG sizes, and see the DC solar cable page for panel strings.
Voltage Drop Questions
How do I calculate voltage drop?
For a single-phase or DC circuit, voltage drop = 2 × resistance per metre × length × current, where the 2 covers the outgoing and returning conductor. For a balanced three-phase circuit use 1.732 instead of 2. In US sizes the calculator above does this with circular mils: VD = 2 × K × I × L / CM. Divide the result by the supply voltage to get the percentage.
What is the allowable voltage drop?
The NEC recommends 3% on a branch circuit and 5% from the service to the farthest outlet, but only as informational notes. BS 7671 in the UK suggests 3% for lighting and 5% for other uses, IEC 60364 gives 4% as an example, and AS/NZS 3000 allows 5% in total. Your equipment may need less, so check its datasheet.
How do I calculate voltage drop for mm² cable?
Use the voltage drop per amp per metre for your cable size, then multiply by the current and the one-way length and divide by 1000. For 4 mm² copper at 70°C that is about 11 mV/A/m, so 20 A over 25 m drops about 5.5 V. The table above lists the values for common sizes. The calculator on this page takes AWG and kcmil sizes, so use the table for metric work.
How do I calculate three-phase voltage drop?
Multiply the current and the one-way length by the resistance per metre and by 1.732 (the square root of 3). The percentage is taken against the line-to-line voltage, for example 400 V, so a 3% limit is 12 V. Choose Three-phase in the calculator above, or use the three-phase column in the table.
How do I check voltage drop on a 12 V DC circuit?
Use the same two-way formula, but remember that 3% of 12 V is only 0.36 V, so a small loss is a big percentage. Short runs of thin wire are the usual cause of dim lights and weak pumps in vehicles, boats and solar systems. Pick DC in the calculator, or see the 12 V example above.
Is voltage loss the same as voltage drop?
Yes. Voltage loss, volt drop and voltage drop all mean the voltage that is used up in the cable between the source and the load.
Does cable temperature change the result?
Yes. Copper resistance rises by about 0.4% for each degree Celsius, so a cable running at 70°C has roughly 20% more resistance than the same cable at 20°C. The tables here assume 70°C conductors, which is a sensible design value for loaded cables.