NEC & Cable SizingNEC 314.16

Box Fill Calculator

Add up conductors, devices, clamps and grounds and compare the total with the volume of the box.

Required volume = (conductors + 2 × devices + 1 clamp + 1 grounds) × volume per conductor (Table 314.16(B))
Calculated Result
—

Step-by-step

  1. Enter valid values to begin.

Volumes are from NEC Table 314.16(A) and (B). Conductors that originate and end in the box and are shorter than 12 in. are not counted; a conductor that loops through unbroken and is at least twice the minimum length counts twice (314.16(B)(1)). This tool assumes all conductors share the size selected.

NEC 314.16 • Tables 314.16(A) & (B) • Box Fill

Box Fill: Counting Wires, Devices and Clamps Before They Cook

Core Engineering Principles

Boxes are sized by volume because a crowded box is a hot box, and a box you can’t close without bending the wires hard is how nicks and shorts happen. The Code assigns each item a volume allowance based on the largest conductor involved, adds it all up, and checks that the box is bigger than the total. The unit is the cubic inch, and the allowance for a conductor goes up as it gets bigger: 14 AWG gets 2.00 in³, 12 AWG gets 2.25, 10 AWG gets 2.50, 8 AWG gets 3.00, and 6 AWG gets 5.00.

The counting rules are what trip people up. Each conductor that enters the box and ends there counts once. A conductor that runs through unbroken counts once too (twice if it’s at least twice the length of the minimum free conductor). Jumpers and pigtails that start and end inside the box, with no part leaving it, don’t count at all. A yoke with a device counts as two conductors, the equipment grounds together count as one, internal clamps count as one, and each fixture stud or hickey counts as one.

Equivalents = conductors + 2 × devices + 1 (all grounds) + 1 (clamps) + 1 × (fittings)
Required volume = Equivalents × volume per conductor (Table 314.16(B)) ≤ box volume (Table 314.16(A))

NEC & Standard References

314.16(A) and its table give the volume of standard metal boxes. A 4 in. square box that is 1-1/2 in. deep is 21 in³, a 4-11/16 in. square, 2-1/8 in. deep box is 42 in³, and a 3 × 2 × 2-3/4 in. device box is 14 in³. For non-standard or nonmetallic boxes, use the volume marked on the box. 314.16(B)(1) through (B)(5) set how each item is counted. 314.16(B)(4) says each yoke counts as two based on the largest conductor connected to it. 314.16(B)(5) says all equipment grounding conductors together count as one, based on the largest. 314.16(C) covers conduit bodies, and 314.28 sets pull-box dimensions.
Worked Example: A Four-Wire Switch Box in a Kitchen
Given: 4 in. × 1-1/2 in. square box (21 in³), 6 insulated 14 AWG conductors, one switch, one ground, no clamps.
1. Conductors: 6 × 1 = 6.
2. Device: 1 yoke × 2 = 2.
3. Grounds: all together = 1.
4. Total equivalents: 6 + 2 + 1 = 9.
5. Volume: 9 × 2.00 = 18 in³ — the 21 in³ box passes with 3 in³ to spare.
Add two more conductors and you’re at 22 in³ and the box fails.
Safety & Installation Rules
  • Use the box marking. A cheap plastic box often holds less than the table says. Read the stamped volume inside it.
  • Mixed sizes. When you have 12 and 14 AWG in the same box, count each at its own allowance. This page assumes one size, so do a second pass for the other.
  • Extension rings and boxes with covers. Raised covers and extensions add volume you may count.
  • Tight boxes run hot. If you have to force the device in, go bigger.
  • Pull boxes and conduit bodies are different. Over 6 AWG the dimensions come from 314.28, not volume.

Volume per Conductor

Volume allowance per conductor (NEC Table 314.16(B)).
AWGVolume (in³)
181.5
161.75
142
122.25
102.5
83
65

How Many Conductors Fit?

Maximum conductors (no devices or clamps) for common boxes.
BoxVolume14 AWG12 AWG10 AWG
3 × 2 × 2-1/2 in. device12.5 in³655
3 × 2 × 3-1/2 in. device18 in³987
4 × 1-1/2 in. square21 in³1098
4 × 2-1/8 in. square30.3 in³151312
4-11/16 × 2-1/8 in. square42 in³211816

Counting Rules

Counting rules.
ItemCounts as
Each insulated conductor1
All grounds together1
Each device yoke (switch, receptacle)2
All internal cable clamps together1
Each fixture stud or hickey1

Worked Example: 12 AWG in a 4 in. Square Box

Six 12 AWG conductors count as 6, one switch counts as 2 and all grounds together count as 1, for 9 equivalents. Volume required is 9 × 2.25 = 20.25 in³. A 4 × 1-1/2 in. square box holds 21.0 in³, so it passes with 0.75 in³ to spare. One more 12 AWG conductor would need 22.50 in³ and the box would fail.

Box Fill Questions

How do I calculate box fill?

Count conductors, devices, grounds and clamps as equivalents, multiply by the volume per conductor, and compare with the box volume.

What counts as two conductors?

Each device yoke, such as a switch or receptacle.

Do grounds count individually?

No. All equipment grounds together count as one.

What if the conductors are different sizes?

Use the volume for each conductor’s own size and add them.

Where do I find the box volume?

Stamped inside the box. Use that value when it is lower than the table.

Can I use a deeper box?

Yes, or an extension ring, if it gives enough volume.