NEC & Cable SizingNEC Article 430

Motor Branch Circuit Calculator

Pick the motor and the protective device to get the full-load current, minimum conductor, breaker or fuse maximum and overload setting.

Icond = 1.25 × FLC  •  Ibreaker,max = 2.5 × FLC  •  Overload = 1.25 × nameplate FLA
Calculated Result
—

Step-by-step

  1. Enter valid values to begin.

FLC values come from NEC Table 430.250 (three-phase) and 430.248 (single-phase), which you must use for sizing conductors and short-circuit protection — not the nameplate. The nameplate current is used only for overload relays. Verify against the adopted NEC edition.

NEC Article 430 • Tables 430.248 & 430.250 • Motor Circuits

Motor Branch Circuits: Why Four Different Numbers Apply to One Motor

Core Engineering Principles

A motor isn’t like a heater. At start it pulls five to eight times its running current for a moment, and the NEC knows that. So it splits the circuit into separate jobs: the conductors carry the running current, the overload relay watches for running overloads, and the branch-circuit short-circuit and ground-fault device is allowed to be much larger than the running current so it doesn’t trip on starting inrush. If you size everything off the nameplate you’ll get at least two of them wrong.

Here is the part that trips people up. For sizing conductors, the breaker and the disconnect, the Code tells you to ignore the nameplate and use the full-load currents in Table 430.250 (three-phase) or 430.248 (single-phase). The nameplate amps are used only for the overload relay. That means two motors with the same HP but different nameplates get identical conductors and breakers.

Conductors: 1.25 × FLC (430.22)  •  Short-circuit device: inverse-time 250% / dual-element fuse 175% / non-time-delay fuse 300% / instantaneous 800% of FLC (Table 430.52)
Overload: 125% of nameplate (SF ≥ 1.15) or 115%  •  Disconnect: ≥ 115% of FLC (430.110)

NEC & Standard References

430.6(A)(1) sends you to the tables for FLC. 430.22 sets the conductor at 125%. 430.52 and Table 430.52 give the maximum short-circuit device, and 430.52(C)(1) Exception 1 lets you round up to the next standard size from 240.6. Exception 2 allows 400% for an inverse-time breaker on motors up to 100 A FLC (300% above 100 A) when the motor won’t start on the smaller size. 430.32 controls the overload, and 430.110 the disconnecting means. For standard sizes check 240.6(A): 15, 20, 25, 30, 35, 40, 45, 50, 60, 70, 80, 90, 100, 110, 125, 150, 175, 200, and so on.
Worked Example: 10 HP, 460 V, Three-Phase Motor
Given: 10 HP, 460 V, 3φ, service factor 1.15, copper conductors at 75°C, inverse-time breaker.
1. Table 430.250: FLC = 14 A.
2. Conductor: 14 × 1.25 = 17.5 A → 14 AWG Cu at 75°C (20 A) works on paper. Most electricians would pull 12 AWG for mechanical strength and the voltage drop on a long run.
3. Breaker: 14 × 2.5 = 35 A → 35 A maximum. If the motor trips on start, the exception allows 4.0 × 14 = 56 A → 60 A.
4. Overload: nameplate FLA 14 A × 1.25 = 17.5 A maximum.
5. Disconnect: 14 × 1.15 = 16.1 A minimum.
Safety & Installation Rules
  • Those are maximums, not targets. The breaker can be smaller than 250%, and often should be if the motor starts fine.
  • Check the nameplate for the overload. Use the real number there, or the table FLC if you don’t have it, and set the relay to what the motor says.
  • VFDs change the rules. Use the drive manufacturer’s input current and Article 430 Part X.
  • Multiple motors: the feeder gets 125% of the largest motor plus the rest at 100% (430.24). This calculator handles one motor.
  • Terminals again: 110.14(C) limits you to the column that matches the lug, even if the wire is rated higher.

460 V Motors

Three-phase 460 V motors, FLC from Table 430.250, copper conductors at 75 °C. Breaker is the 250% maximum rounded up to a standard size (430.52).
HPFLCConductor 125%WireBreaker maxOverload 125%
12.1 A2.6 A14 AWG15 A2.6 A
34.8 A6.0 A14 AWG15 A6.0 A
57.6 A9.5 A14 AWG20 A9.5 A
1014 A17.5 A14 AWG35 A17.5 A
1521 A26.2 A10 AWG60 A26.2 A
2534 A42.5 A8 AWG90 A42.5 A
5065 A81.2 A4 AWG175 A81.2 A
100124 A155.0 A2/0 AWG350 A155.0 A

230 V Motors

Three-phase 230 V motors, FLC from Table 430.250, copper conductors at 75 °C. Breaker is the 250% maximum rounded up to a standard size (430.52).
HPFLCConductor 125%WireBreaker maxOverload 125%
14.2 A5.2 A14 AWG15 A5.2 A
39.6 A12.0 A14 AWG25 A12.0 A
515.2 A19.0 A14 AWG40 A19.0 A
1028 A35.0 A10 AWG70 A35.0 A
1542 A52.5 A6 AWG110 A52.5 A
2568 A85.0 A4 AWG175 A85.0 A
50130 A162.5 A2/0 AWG350 A162.5 A

Worked Example: 25 HP, 230 V, Three-Phase

Table 430.250 gives FLC = 68 A. Conductors need 1.25 × 68 = 85 A, so 4 AWG copper at 75 °C (85 A). The inverse-time breaker maximum is 2.5 × 68 = 170 A, rounded up to 175 A. The overload relay is set at no more than 1.25 × nameplate FLA (about 85 A if the nameplate matches the table). The disconnect must be at least 115% of FLC, 78.2 A. Use the nameplate for the overload, and the table value for conductors and breaker.

Motor Circuit Questions

How do I size motor branch-circuit conductors?

125% of the table FLC from Table 430.250.

What is the maximum breaker size?

Typically 250% of FLC for an inverse-time breaker, rounded up to the next standard size, with higher allowances if the motor will not start.

Where does the overload setting come from?

From the nameplate FLA, usually 115% or 125% depending on service factor and temperature rise.

Table FLC or nameplate?

Use the table value for conductors, breaker and disconnect, and the nameplate for overload.

Do VFDs change this?

Yes, follow the drive manufacturer and 430.122 for conductor sizing.

Are these maximums?

Yes. A smaller breaker is fine if the motor starts reliably.