NEC & Cable SizingNEC 250.122

Equipment Grounding Conductor Calculator

Choose the breaker or fuse rating to get the minimum equipment grounding conductor for copper or aluminum.

EGC = Table 250.122 (OCPD rating)  •  upsized: AEGC = Atable × (CMinstalled / CMoriginal)
Calculated Result
—

Step-by-step

  1. Enter valid values to begin.

Table 250.122 lists minimum EGC sizes by overcurrent device rating. When conductors are upsized, 250.122(B) says the EGC grows in the same proportion of circular mils. Circular-mil values: 14 AWG 4,110 • 12 AWG 6,530 • 10 AWG 10,380 • 8 AWG 16,510 • 6 AWG 26,240 • 4 AWG 41,740.

NEC Table 250.122 • 250.122(B) • Equipment Grounding Conductor

Equipment Grounding Conductor: The Wire That Makes the Breaker Trip

Core Engineering Principles

When a hot wire touches a metal enclosure, the enclosure becomes live. Unless there is a low-impedance path back to the source, the breaker never sees enough current to trip, and the next person to touch the box becomes the path. The equipment grounding conductor is that path. It bonds every enclosure and frame to the system neutral at the source. A ground fault then becomes a short circuit with hundreds or thousands of amps and the breaker clears it in a fraction of a second. That’s why the EGC is sized from the breaker or fuse protecting the circuit, not from the load.

It also has to survive. During those few cycles before the breaker clears, the wire carries a very high current and can melt if it’s too small. Table 250.122 gives the minimum size for each overcurrent device rating. Bigger breaker, bigger EGC.

EGC = Table 250.122 (rating of the overcurrent device ahead of the circuit)
Upsized conductors: AEGC = Atable × (CMinstalled / CMoriginal)  •  Never larger than the circuit conductors

NEC & Standard References

Table 250.122 reads “not exceeding” each rating: 15 A takes 14 AWG Cu, 20 A takes 12 AWG, 60 A takes 10 AWG, 100 A takes 8 AWG, 200 A takes 6 AWG, 400 A takes 3 AWG, and 800 A takes 1/0 AWG. 250.122(B) says if you upsize ungrounded conductors for any reason (voltage drop is the usual one) the EGC has to be increased in the same proportion of circular mils. 250.122(A) says you never need an EGC bigger than the circuit conductors. 250.122(F) requires a full-size EGC in each raceway when you parallel conductors, and 250.118 lists which raceways and cable armor are acceptable as the path. An EGC may be bare, covered or insulated, and insulated ones must be green or green with yellow stripes.
Worked Example: 20 A Branch Circuit, Upsized for Voltage Drop
Given: A 20 A breaker feeds a long barn circuit. The copper conductors were increased from 12 AWG (6,530 CM) to 8 AWG (16,510 CM) for voltage drop.
1. Table 250.122: 20 A → 12 AWG Cu (6,530 CM).
2. Upsize factor = 16,510 / 6,530 = 2.53.
3. EGC area = 6,530 × 2.53 = 16,510 CM → 8 AWG Cu.
4. 250.122(A) says it never has to be larger than the circuit conductors (8 AWG), so 8 AWG is the final answer.
Safety & Installation Rules
  • Don’t forget 250.122(B). It’s the one inspectors catch on long runs where wire was bumped up two sizes.
  • Metal conduit is not always a ground. Flexible conduit longer than six feet needs a wire, and flex on vibrating equipment is best always run with a wire.
  • Same raceway. Run the EGC with the circuit conductors, not separately, or the impedance goes up and the breaker might not trip.
  • Isolated grounds are the exception. An insulated ground for sensitive loads still must connect back to the source and the enclosure per 250.146(D).
  • Never use the neutral as a ground downstream of the service. That puts current on the metal.

Equipment Grounding Conductor Sizes

Copper EGC from NEC Table 250.122 (check the adopted edition).
Overcurrent device (not exceeding)Copper EGC
15 A14 AWG
20 A12 AWG
30 A10 AWG
40 A10 AWG
60 A10 AWG
100 A8 AWG
200 A6 AWG
300 A4 AWG
400 A3 AWG
500 A2 AWG
600 A1 AWG
800 A1/0 AWG
1000 A2/0 AWG

When You Upsize the Circuit Conductors

The EGC must grow by the same proportion, but never larger than the circuit conductors.

Upsizing factor under 250.122(B) when a 20 A circuit (12 AWG, 6,530 CM) is built with larger conductors.
Installed conductorFactor = CM installed / 6,530
20 A breaker, 12 AWG installed1.00
20 A breaker, 10 AWG installed1.59
20 A breaker, 8 AWG installed2.53
20 A breaker, 6 AWG installed4.02

Worked Example: 30 A Circuit Upsized from 10 AWG to 6 AWG

A 30 A breaker takes a 10 AWG copper EGC (10,380 CM). The circuit conductors were raised from 10 AWG to 6 AWG (26,240 CM) for voltage drop, a factor of 2.53. The EGC area becomes 10,380 × 2.53 = 26,240 CM, which rounds up to 6 AWG. That equals the circuit conductor size, so 250.122(A) allows it to stop there.

EGC Questions

What size EGC for a 20 A circuit?

12 AWG copper under Table 250.122.

Is the EGC sized from the load?

No. It is sized from the rating of the breaker or fuse protecting the circuit.

When must the EGC be increased?

When the ungrounded conductors are upsized, for example for voltage drop. The EGC grows in the same proportion of circular mils.

Does the EGC ever need to be larger than the circuit conductors?

No, 250.122(A) caps it at the size of the circuit conductors.

What about parallel conductors?

Each raceway needs a full-size EGC sized from the overcurrent device.

Can conduit be the EGC?

Some types can under 250.118. Flexible conduit on vibrating equipment is best run with a wire.